MEGA-iAdvantage

The purpose-built 30-storey data center building is equipped with state-of-the-art infrastructure and a genuine resilient global network, which can be tailor-made for customers’ different power and deployment specifications. Being a genuine carrier neutral data center solution provider, they are now operating as a Global Telecom Hub in Hong Kong with over 100 Global and China carriers connecting 9 submarine cable systems from all over the world. This gives our customers freedom of choice to select their preferred network service provider.

Overview

Location:
399 Chai Wan Road
Chai Wan, Hong Kong

14 minutes from Central
40 minutes from HK International Airport
43 minutes from Lo Wu Cross-Border

Power:

  • Power connection: Dual power feeds / UPS sources to rack

  • UPS: 2N redundant configuration

  • Voltage: 220V / single-phase, 50Hz

  • Power provision: Standard power zone: average 1.5kVA per rackHigh power zone: upto 3kVA per rack

  • Generator sets: 2N design

  • Backup diesel: Multiple fuel tanks of capacity 48,000 liters

  • Power auto switch: Dual static-transfer-switch per zone

Air Conditioning:

  • CRAC: N+1 CRAC designDown flow systems with hot and cold aisles design

  • Chillers plant: Dual distribution path through dual feed independent chiller riser

  • Temperature: 22+/- 2 degree Celsius

  • Humidity: 50 +/- 10%

Building:
Purpose-built Data Centre building

  • Data center area (GFA): About 350,000 sq. ft.

  • Floor height: 4.1m (3.5m under beam)

  • Floor loading: 5-7.5 kPa

  • Capacity: >4,000 racks in common areas / private cage

  • Rack size: 42U, 45U, 48U racks

Fire Protection:
Fire suppression:

  • Gas based FM200 / Inergen fire suppression system

  • Double interlock pre-action sprinkler

Security:

  • Surveillance monitoring: 24 hours surveillance CCTV with digital recording

  • 24/7 On-site security presence

  • Building security: 24 hours entrance security guards to control access

  • Access control: Access control system

Connectivity:
Networks:

  • Dual feed building lead in for telecom cable access

  • 2 x Telecommunications Broadcasting Equipment rooms

  • Exchange hub for telecom carrier interconnection

  • Data cable access: Cat5E, Cat 6, SM/MM fiber, DS3, E1, Coaxial